Item
|
KM-N2-FLK
|
Measured items
|
Total power consumption (active, regenerative, and reactive), power (active and reactive), current, voltage, power factor, and frequency
|
Measurement specifications
|
Active power
|
0.5% (IEC 62053-22 class 0.5S)
|
Reactive power
|
2% (IEC 62053-23 class 2)
|
Sampling cycle
|
80 ms for 50 Hz and 66.7 ms for 60 Hz
|
Insulation resistance
|
- Between all electrical circuits and the case: 20 MΩ min. (at 500 VDC)
- Between all power supply and voltage inputs and all communications and pulse output terminals: 20 MΩ max. (at 500 VDC)
|
Dielectric strength
|
|
- Between all electrical circuits and the case: 2,200 VAC for 1 min
- Between all voltage and current inputs and all communications and pulse output terminals: 2,200 VAC for 1 min
|
Vibration resistance
|
Single amplitude: 0.1 mm, Acceleration: 15 m/s2, Frequency: 10 to 150 Hz, 10 sweeps for 8 min each along three axes
|
Shock resistance
|
150 m/s², 3 times each in 6 directions (up/down, left/right, forward/backward)
|
Indications and operation method
|
LED/LCD indications and operation buttons
|
Weight
|
Approx. 350 g (Power Monitor only)
|
Degree of protection
|
IP20
|
Pulse output
|
Number of outputs
|
Number of outputs: 4 (photoMOS relay outputs)
Used for the total power consumption pulse output.
|
Output capacity
|
50 mA at 40 VDC
ON residual voltage: 1.5 V max. (for output current of 50 mA)
OFF leakage current: 0.1 mA max.
|
Output unit
|
Output unit: 1, 10, 100, 1k, 5k, 10k, 50k, or 100k (wh)
Pulse ON time: 500 ms (Cannot be changed.)
|
Communications interface
|
Communications method
|
RS-485 (2-wire half-duplex with start-stop synchronization)
|
Communications protocol
|
Modbus (RTU): Binary. CompoWay/F: ASCII
|
Baud rate
|
1.2, 2.4, 4.8, 9.6, 19.2, or 38.4 kbps
|
Data length
|
Data length: 7 or 8 bits
Stop bits: 1 or 2 bits
Vertical parity: Even, odd, or none
|
Maximum transmission distance
|
1,200 m
|
Maximum number of connected Power Monitors
|
Modbus: 99, CompoWay/F: 31
If you measure more than one circuit with one Power Monitor, the number of circuits is treated as the number of connected Power Monitors.
|
Dimensions (H×W×D)
|
90 × 90 × 65 mm (excluding protrusions)
|
Installation method
|
DIN Rail mounting
|
Accessories
|
Instruction Manual and Compliance Sheet
|